Publication:
Numerical Investigation on Auxiliary Heat Sources for Horizontal Ground Heat Exchangers

dc.contributor.authorAlexandru-Mihai BULMEZ
dc.contributor.authorVasile CIOFOAIA
dc.contributor.authorGabriel NĂSTASE
dc.contributor.authorGeorge DRAGOMIR
dc.contributor.authorAlin-Ionuț BREZEANU
dc.contributor.authorNicolae-Fani IORDAN
dc.contributor.authorSorin-Ionuț BOLOCAN
dc.contributor.authorMariana FRATU
dc.contributor.authorCostel PLEȘCAN
dc.contributor.authorChristiana Emilia CAZACU
dc.contributor.authorOvidiu DEACONU
dc.date.accessioned2025-09-12T13:38:49Z
dc.date.issued2022
dc.description.abstractHuman interference with the Earth’s climate cannot be ignored any longer. Renewable energy sources need utmost attention in all energy sectors. For buildings, geothermal energy for heating, cooling, and domestic hot water is a sustainable solution. Horizontal ground heat exchangers (HGHE) demonstrate promising results with low installation costs. Research is focused on increasing their thermal performances by structural improvements and ground thermal proprieties improvements, with little research on using auxiliary heat to increase their performances. A numerical model for an HGHE was established to investigate the effects of auxiliary heat sources on the performances of the HGHE. The results demonstrate that heat transfer into the HGHE increases the overall ground temperature at the end of the heating season by 138.50% compared with no heat transfer from auxiliary heat sources. The ground freezing period decreased by approximately 24.74% by having a heated basement, approximately 40.20% by transferring heat with solar thermal panels, and approximately 62.88% by using both auxiliary heat sources. The difference between the undisturbed ground temperature and the ground temperature with no auxiliary heat sources at the end of the season was 3.45 C. The difference between the undisturbed ground temperature and the ground temperature with all auxiliary heat sources resulted in 0.92 °C.
dc.identifier.urihttps://doi.org/10.3390/buildings12081259
dc.identifier.urihttps://repository.unitbv.ro/handle/123456789/1041
dc.language.isoen
dc.publisherMDPI; Buildings
dc.titleNumerical Investigation on Auxiliary Heat Sources for Horizontal Ground Heat Exchangers
dc.typeArticle
dspace.entity.typePublication

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Numerical Investigation on Auxiliary Heat Sources for Horizontal Ground Heat Exchangers.pdf
Size:
6.82 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
2.35 KB
Format:
Item-specific license agreed to upon submission
Description: